  "schema_version": "1.0",
  "rubrics": [
    {
      "id": "R1",
      "requirement": "The drawing shall show a horizontal 11 kV feeder line with a left-end arrowhead labelled \"UTILITY 11KV\"."
    },
    {
      "id": "R2",
      "requirement": "The drawing shall show two transformer branches, each with a drop-out fuse drawn as arcs, a transformer of two circles with triangles, and a Q0 breaker."
    },
    {
      "id": "R3",
      "requirement": "The drawing shall show a lightning arrester labelled \"LA\" on each transformer branch."
    },
    {
      "id": "R4",
      "requirement": "The drawing shall show an EMDB-01 busbar with exactly four outgoing feeders, each with a breaker and a terminating arrow."
    },
    {
      "id": "R5",
      "requirement": "The drawing shall show an LDB-02 busbar with exactly seven outgoing feeders, each with a breaker and a terminating arrow."
    },
    {
      "id": "R6",
      "requirement": "The drawing shall include an APFC/CAP BANK box connected to the LDB-02 busbar, and a METERING element with a V5 box and an \"A\" meter."
    },
    {
      "id": "R7",
      "requirement": "The drawing shall label the transformers \"TR-1\" and \"TR-2\" with 433V, label the breakers \"Q0 160A\" and \"Q0500A\", and label the incomers \"ACB INCOMER 3P 630A\" and \"ACB INCOMER 3P 400A\"."
    },
    {
      "id": "R8",
      "requirement": "The drawing shall label the feeders with their ratings: EMDB-01 F1 160A, F2 160A, F3 200A, F4 63A; LDB-02 F1 32A, F2 100A, F3 250A, F4 125A, F5 100A, F6 63A, F7 63A."
    },
    {
      "id": "R9",
      "requirement": "The drawing shall label the feeder cables with load names and sizes, including OT DB 4CX25MM2, ICU DB 4CX70MM2, LIFE SAFETY 4CX50MM2, UPS INPUT 4CX95MM2, HVAC DB 4CX25MM2, LIFT DB 4CX70MM2 and SPARE 4CX25MM2."
    },
    {
      "id": "R10",
      "requirement": "The drawing shall include the board tags \"EMDB-01\" and \"LDB-02\", the notes \"EXISTING\" and \"NEW INSTALLATION\", and the text \"12 STEP 100KVA\"."
    },
    {
      "id": "R11",
      "requirement": "The drawing shall contain layers E-ONEL (ACI 7, Continuous, 0.35 mm), E-ONEL-SYMB (ACI 4, Continuous, 0.25 mm), E-ANNO-TEXT (ACI 3, Continuous, 0.25 mm) and E-ANNO-TTLB (ACI 7, Continuous, 0.25 mm)."
    },
    {
      "id": "R12",
      "requirement": "The drawing shall place all schematic lines, circles and arcs on layer E-ONEL."
    },
    {
      "id": "R13",
      "requirement": "The drawing shall place all text (MTEXT) on layer E-ANNO-TEXT."
    },
    {
      "id": "R14",
      "requirement": "The drawing shall define block LIGHTNING-ARRESTER and insert it 2 times on layer E-ONEL-SYMB, once for each arrester."
    },
    {
      "id": "R15",
      "requirement": "The drawing shall define block CAPACITOR-STEP and insert it 2 times on layer E-ONEL-SYMB within the APFC bank."
    },
    {
      "id": "R16",
      "requirement": "The drawing shall insert the title block blocks NO_NUM_acade_title and WD_M once each on layer E-ANNO-TTLB."
    },
    {
      "id": "R17",
      "requirement": "The drawing shall have every object's colour, linetype and lineweight set to ByLayer."
    },
    {
      "id": "R18",
      "requirement": "The drawing shall have no drawing geometry on layer 0."
    }
  ]
}